Skip to content

fdia-graph

PyPI Python 3.9+ Tests License: MIT code, CC BY 4.0 data

Labelled cyber-attack data for power-grid research, and the code that makes it.

fdia-graph builds timelines of meter readings on power-grid test systems, places false data injection attacks (FDIA) in them, and labels the buses each attack targets. The generator solves every attack it makes on the AC power-flow equations, around the buses it targets. Download a ready timeline, or generate your own.

Two panels, one per target branch of an overload attack on IEEE-14, apparent flow in MVA against the frame. Outside the attack window the reported flow follows the flow without the attack. Inside the 60-frame window the reported flow climbs steadily to the branch's rating, shown as a dotted line, while the flow without the attack stays near where it was.

One overload attack in a generated IEEE-14 timeline, as an operator would see it. Over 60 frames the flow meters of two branches report a flow that climbs to the rating, while the flow without the attack stays near where it was. python examples/first_look.py makes this figure, fdia-graph in five cells is a notebook that generates the same timeline and draws the same flows, and Follow one attack through the code explains every step behind it.

Three steps

1. Load a released dataset.

import fdia_graph as fg

# downloads the IEEE-118 timeline once, then caches it
train = fg.load("ieee118", split="train")
arrays = train.export()
print(arrays["node_x"].shape, arrays["y"].shape)

2. Generate your own, then load it by name.

# needs fdia-graph[generate]
# downloads the IEEE-14 pool of solved operating points
# about five minutes on a laptop
fg.generate("ieee14", name="my_run", frames=2000)
mine = fg.load("my_run", split="train")

3. Analyse it with an estimator.

# needs fdia-analysis[se]
from fdia_analysis.se.methods import WLS

test = fg.load("ieee118", split="test")
est = WLS().fit(train)
print(est.score(test))

Two toolkits

Toolkit Package What it does
fdia-graph fdia_graph generates a timeline and loads it
fdia-analysis fdia_analysis runs estimators and localizers on a timeline

fdia-analysis holds state estimation, attack localization, federated training, trusted-meter selection and a results store. It depends on fdia-graph. fdia-graph never imports it.

Test systems

System Buses Data
IEEE and other public cases 14, 30, 57, 89, 118, 145, 200, 300 released datasets, downloaded by fg.load
New York grid 140 case file in the package; you build the dataset

Each released dataset is one timeline of 72,000 frames. The New York grid is a MATPOWER case file with 140 buses and 227 branches. It goes through the same generator, and Build the operating points starts its dataset.

The generator makes two attack families: At, a slow load ramp, and Am, a line overload. The released files hold seven families: five that the generator does not make (Aq, Ad, As, Ar, Al), and an Am that drives no line to its limit. The attack families has the details.

How it flows

Six stages, top to bottom. 1. Test system: Case, Network. 2. Operating points: generate_states for the IEEE cases, PoolBuilder for New York. 3. Meters and attacks: MeterPlan, NoiseModel, the attack designs. 4. Timeline file: TimelineSource.generate, TimelineWriter. 5. Load: fg.load returns FdiaGraph. 6. Analyse: fdia_analysis.

Install

Command Gives
pip install fdia-graph the loader: opens a timeline, exports splits as numpy arrays
pip install "fdia-graph[torch]" adds PyTorch: single records, batches and the DataLoader
pip install "fdia-graph[generate]" adds pandapower, to generate timelines
pip install "fdia-analysis[se]" the analysis toolkit with state estimation

Every extra of both toolkits is listed in Install and data versions.

Where next

Citation

  • Al (released files) and the load bound of Am: Yuan, Li & Ren, Modeling load redistribution attacks in power systems, IEEE T-SG 2(2), 2011.
  • At: Haghshenas, Hasnat & Naeini, A Temporal GNN for Cyber Attack Detection and Localization in Smart Grids, IEEE ISGT 2023.
  • Measurement model: Zaman & Lin, PING: Physics-Informed GNNs to Generalize FDIA Localization, NAPS 2025.
  • Meter noise: Asprou, Kyriakides & Albu, Variable Weights in a WLS State Estimator, IEEE T-IM 63, 2014.
  • Protocol: Boyaci et al., Joint Detection and Localization of Stealth FDIA, IEEE T-SG, 2022.
  • Local false states, Am, trusted meters: Wu, Wang, Hu, Ye & Tang, Dynamic PMU configuration for stealthy multi-snapshot FDIA mitigation, IEEE T-SG 17(1), 2026.

License

Data under CC BY 4.0, code under MIT (see LICENSE). Synthetic, from public IEEE cases. Not for operational decisions.